Operating Instructions SWT-2000 DYNALCO
5
Sensor monitoring 3 sensor monitoring settings are available in the configuration software:
No Sensor Monitoring
Monitoring of supplied sensors (active Sensor Types)
[Also for 2 wire sensors that are supplied via the internal Pull-up resistor (1kΩ)
Æ Sensors drawing current outside of I
min
or I
max
are considered to be faulty.
I
min
= 0.5…35mA
I
max
= 0.5…35mA
Monitoring of non powered sensors (passive Sensor Types)
[For 2 wire sensors such as electromagnetic sensors.]
Æ The sensor is considered to be faulty if the line is broken.
Here the sensor impedance is dynamically measured.
Z < 60 kΩ = OK
Z > 125 kΩ = NOT OK
2.3 Binary Inputs
Number 2 Active Binary Inputs and 1 push button (FUNC – logic OR with Binary input B1)
Level Logic 0 = 0V….+5V
Logic 1 = +15V….+36V
Isolation voltage 1500 V
RMS
Input resistance
R
min
= 8.2 kΩ
2.4 Outputs
2.4.1 Analog Outputs
Number 2 Analog outputs
Isolation voltage 1000 VDC
Output type Current (selectable 0…20 / 4…20mA)
Load
Max. 500Ω
Open circuit voltage Max. 15V
Typical error curve
-1
-0.9
-0.8
-0.7
-0.6
-0.5
-0.4
-0.3
-0.2
-0.1
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0.00E+00
1.00E-03
2.00E-03
3.00E-03
4.00E-03
5.00E-03
6.00E-03
7.00E-03
8.00E-03
9.00E-03
1.00E-02
1.10E-02
1.20E-02
1.30E-02
1.40E-02
1.50E-02
1.60E-02
1.70E-02
1.80E-02
1.90E-02
2.00E-02
I (A)
Measurement error (%)
0.2 % (from measured value) + 2 LSB
CLASS 0.1 % (from End Value)
Vedere la pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 34 35

Commenti su questo manuale

Nessun commento